100 MM.Ø SCHEDULE 40 PVC WASTE STACK/SEWER STACK
6759 22' - 2"
INDIVIDUAL REAR YARD
PVC TRUNKING COVER FOR INSULATED REFRIGERANT LINES FROM AC CLG #01 UNIT
20 MM.Ø PVC CONDENSATE DRAIN PIPE TAPPED TO UTILITY SINK DRAIN
ACCU # 01
100 MM.Ø PVC DOWNSPOUT/ ROOF DRAIN TO BOX DRAIN AT REAR OF PROPERTY
IS
FLUSHED TYPE EXTRACTOR VENT DI F F USER S
LANDSCAPED AREA
AC CLG # 01
INSULATED REFRIGERANT PIPES INSIDE CEILING
POWER SUPPLY LINE FOR AC ACCU INSIDE 12.5MM.Ø PVC CONDUIT PIPE INSTALLED IN CEILING
DRYWALL CLADDING OF SANITARY PIPE & PIPE VENT PROVIDE ACCESS PANEL/ MECHANISM
LIVING AREA
LAUNDRY
100 MM.Ø PVC VENT PIPE
INSIDE CEILING
EF
EXTRACTOR FAN INSTALLED AT CEILING LEVEL
POWDER RM. STORAGE
ISOLATION SWITCH
PROPOSED CLADDING PANELS FOR EXPOSED PIPES
INSULATED REFRIGERANT PIPES ONSIDE PVC TRUNKING
100MM.Ø S-40 PVC WASTE STACK AND VTR
POWER LINE INSIDE 12MM.Ø PVC CONDUIT PIPE INSIDE CEILING - TO ISOLATOR SWITCH AT ROOFDECK
3988
13' - 1"
2589 8' - 6"
6759 22' - 2"
3870 12' - 8"
INSULATED REFRIGERANT PIPELINE INSIDE CEILING AND ATTACHED TO UNDERSIDE OF ROOF DECK SLAB AND TAPPED TO ACCU RISER TRUNKING
INSULATED REFRIGERANT PIPELINE INSIDE CEILING AND ATTACHED TO UNDERSIDE OF ROOF DECK SLAB AND TAPPED TO ACCU RISER TRUNKING
FLUSHED TYPE EXTRACTOR VENT DIFFUSERS
wc
wb
sh.
100 MM.Ø PVC VENT PIPE INSIDE CEILING
wb
MASTER’S BATH & CLOSET GF16
AC CLG # 02
20 MM.Ø CONDENSATE DRAIN PIPE TAPPED TO WASH BASIN DRAIN PIPE
MASTER’S BEDROOM GF17
10870
35' - 8"
MAIN STAIRCASE
PANTRY
EF
wb
wc
1
UP
2
3
4
5
6
7
8
1831
6' - 0"
EXTRACTOR FAN INSTALLED AT CEILING LEVEL
sh.
COMMON BATH GF14
H A L L
19
MAIN STAIRCASE
18
17
16
15
14
13
UP
12
OPEN SPACE
DINING AREA
EXTRACTOR FAN INSTALLED AT CEILING LEVEL
RANGE HOOD
MAIN KITCHEN
WALL TYPE OVEN
& MICROWAVE
EF
100 MM.Ø PVC VENT PIPE OR FLEX TUBE INSIDE CEILING
100 MM.Ø SHEDULE 40 - PVC SEWER/ SOUIL PIPE
50 MM. GREY WATER PIPE @ GRADE LEVEL
LANDSCAPED AREA
LANDSCAPED AREA
FLASE COLUMN IN DRYWALL CLADDING
USING CEMENT BOARDS ON METAL STUDS FRAMING\ PROVIDE ACCESS PANEL AT LOWER PORTION
ONE STEP ENTRY UP
1635 5' - 4"
FRONT YARD
FLUSHED TYPE EXTRACTOR VENT DIFFUSERS
1524 MM. WIDE CONCRETE SIDEWALK
4704
15' - 5"
BEDROOM−03 GF12
BEDROOM−02 GF13
CONDENSATE DRAIN PIPE FOR ACU CLG#03 EMBEDDED IN WALL DRAINED TO KITCHEN GREY WATER LINE
POWER LINE TO ACCU & ISOLATOR SWITCH @ ROOF DECK LEVEL
100 MM.Ø PVC DOWNSPOUT W/ PIPE CLADDING COVER USING PRE-PAINTED 20 GA BENDED METAL SHEETS
INSULATED REFRIGERANT LINE FROM AC CLG#04 TO ROOF DECK ACCU
AC CLG # 04
20 MM. Ø PVC CONDENSATE DRAIN PIPE FOR AC CLG#04
INSULATED REFRIGERANT LINE FROM AC CLG#03 TO ROOF DECK ACCU
AC CLG # 03
2
M−01
FIRST FLOOR MECHANICAL PLAN
1 : 50
597
1' - 11"
RC WHEEL STOP
5500
18' - 1"
PARKING BAYS
1
2
3
1
M−01
6000 MM. WIDE PAVED DRIVEWAY
GROUND FLOOR MECHANICAL PLAN
1 : 50
6759 22' - 2"
75MM.Ø PVC RAINLEADER/DOWNSPOUT
100 MM.Ø PVC WASTE STACK
WEATHERPROOF ISOLATOR SWITCH WITH INSULATED POWER LINES INSIDE PVC CONDUIT RISER FROM FIRST FLOOR ACU UNIT
IS
ROOF PLANTERS
ACCU# 2
20 MM.Ø PVC CONDENSATE DRAIN EMBEDDED TO WALL & DRAINED TO ROOF DECK FULLBORRE
100 MM.Ø PVC WASTE STACK
100 MM. Ø VTR W/ VENT CAP
ROOF DRAIN
ROOF DRAIN W/ 75 MM. Ø PVC RAINLEADER
OR DOWNSPOUT UNDER FULLBORRE
INSULATED REFRIGERANT PIPELINE
FROM FIRST FLOOR ACU & INSIDE
PVC TRUNKING TO ACCU
VTR
MAIN STAIRCASE
INSULATED REFRIGERANT PIPELINE FROM FIRST FLOOR ACU & INSIDE PVC TRUNKING TO ACCU
POWER LINE TO ACCU & ISOLATOR SWITCH @ ROOF DECK LEVEL
WEATHERPROOF ISOLATOR SWITCH WITH INSULATED POWER LINES INSIDE PVC CONDUIT RISER FROM FIRST FLOOR ACU UNIT
PVC CONDENSATE DRAIN PIPE
FOR AC CLG#03 EMBEDDED TO WALL & DRAINED AT GRADE LEVL
IS
305 1' - 0"
ROOF DRAIN W/ 100 MM. Ø PVC RAINLEADER/ DOWNSPOUT UNDER FULLBORRE
INSULATED REFRIGERANT PIPELINE FROM FIRST FLOOR ACU & INSIDE PVC TRUNKING TO ACCU
ACCU# 3
20 MM.Ø PVC CONDENSATE DRAIN EMBEDDED TO WALL DRAINED TO FULLBORRE
3
M−01
ROOF DECK MECHANICAL PLAN
1 : 50
IS
ACCU# 4
305 1' - 0"
1691
5' - 7"
3456
11' - 4"
LEGEND:
AC CLG # 01
INDOOR AC INVERTER UNIT
ACCU#01
OUTDOOR AIRCON CONDENSING UNIT FLOOR OR WALL MOUNTED
EF
EXTRACTOR FAN INSIDE CEILING 100 MM. Ø PVC VENTILATION PIPE
AIR FLOW DIRECTION
FLUSHED TYPE EXTRACTOR VENT DIFFUS E R S
INSULATED REFRIGERANT
PIPELINE & RISER INSIDE PVC DUCT
COLD WATER DRAIN PIPE
FROM INDOOR AC UNIT
POWER SUPPLY CABLE
INSIDE PVC CONDUIT PIPE
1981
6' - 6"
3905
12' - 10"
1910
6' - 3"
WEATHERPROOF ISOLATOR SWITCH WITH INSULATED POWER LINES INSIDE PVC CONDUIT RISER FROM FIRST FLOOR ACU UNIT
NOTES:
GENERAL:
1.ALL WORKS TO BE CONSTRUCTED BY A
SANITARY CONSTRUCTOR LICENSED BY
THE WATER AND SEWAGE AUTHORITY OF
TRINIDAD & TOBAGO.
2.ALL WORKS SHALL COMPLY WITH: THE
NATIONAL PLUMBING CODE OF TRINIDAD
& TOBAGO.
3.
THE LICENSED SANITARY CONSTRUCTOR SHALL ENSURE THAT WASA'S
REPRESENTATIVE SHALL INSPECT AND APPROVE ALL STAGES OF THE WORKS AND SHALL OBTAIN FINAL APPROVAL.
4.ALL GRAVITY PIPES AND FITTINGS SHALL
MEET THE REQUIREMENTS AND COMPLIANT
WITH ASTM 2665
5.ALL PRESSURE PIPES :AND FITTINGS
SHALL BE PVC SCHEDULE 40.
POTABLE WATER SYSTEM :
1.ALL MATERIALS SHALL CONFORM WITH
THE FOLLOWING BRITISH OR EQUIVALENT
AMERICAN STANDARDS CODES.
(A) BS EN 1452-1: 2000 GENERAL
(B) BS EN 1452-2: 2000 PIPES
(C) BS EN 1452-3: 2000 FITTINGS
2.ALL FIXTURES ARE TO BE PROVIDED
WITH ANGLE GATE VALVES
3.THE OVERFLOW TO ALL WATER CLOSETS
TO BE PIPED TO THE OUTSIDE OF THE
BUILDING.
4.EACH SUPPLY BRANCHES SHALL HAVE AN
ISOLATING GATE VALVES.
5.ALL PIPES ARE TO BE PRESSURE TESTED
AND CAPPED OFF IN SEGMENTS BEFORE
COVER UP AND FINAL COMMISIONING.
DRAIN, WASTE & VENT SYSTEM
ALL PRESSURE PIPES AND FITTINGS
1.
SHALL BE PVC SCHEDULE 40.
2.ALL PIPES UNDER BUILDING OR UNDER
CONCRETE SLAB TO BE SCHEDULE-80
PVC PIPES.
3.GRADES TO PIPE AS FOLLOWS:
(A)100∅ PIPE = 4 : 300
(B)150∅ PIPE = 6 : 300
4.CLEANOUT TO BE PLACED EVERY
1500MM APART.
DRAWING ISSUE:
PROMOTIONAL INFORMATION
RE VISION:
ISSUE: REVISION:
DATE
MM:DD:YY
DRAWING TITLE:
MECHANICAL FLOOR PLANS
DESIGNED DRAWN CHECKED
DATE
SCALE
PROJECT:
APR / RFMaraya LITEDARCH
D Bro ok s
Issue Date
1 : 50
20 No. TOWNHOUSES
DRWG.#
M-01
T.Q. REF.#
EverGreen by Andoma
Lot Nos. 1 & 2a,
Warren Road, Chaguanas.
CLIENT:
APR ASSOCIATES LIMITED
32 AGOSTINI STREET, ST. JOSEPH
APR ASSOCIATES LIMITED E P MANAGERS.
NGINEERS &ROJECT
#32 Agostini Street,
St. Joseph,
Trinidad West Indies. Phone:(868) 663-5171
Fax: (868) 662-1667
TOP OF PARAPET WALL 9775
75MM. Ø FULLBORRE ROOF DRAIN
8' - 9"
2671
TOP OF ROOF DECK 710475MM.Ø PVC DOWNSPOUT BEHIND
MASONRY WALL
PROVIDE DRYWALL CLADDINGH
304 1' - 0"
ACCU W/ 100 MM. HT. CONCRETE PLINTH
AC CLG#04 OUTLINE
ACCU W/ 100 MM. HT. CONCRETE PLINTH
BLOCKWALL RAILING HEIGHT
RECOMMENDED CEILING LEVEL
AC CLG#03 OUTLINE
1050
3' - 5"
10' - 8"
3239
20 MM. Ø PVC CONDENSATE DRAIN TAPPED TO DOWNSPOUT
FIRST FLOOR LEVEL 3865
9' - 0"
2749
DIFFUSER FOR EXTRACTOR FAN W/
100 MM.Ø PVC VENT PIPE INSIDE CEILING
11' - 7"
3539
RECOMMENDED CEILING LEVEL
20 MM. Ø PVC CONDENSATE DRAINS EMBEDDED IN CONCRETE WALL AND
DRAIN TO GREY WATER PIPE AT
PARKING LEVEL
9' - 5"
2867
Ground Floor Level
326
Parking Level
26
100 MM. Ø PVC RAIN WATER DISCHARGE PIPE
100 MM. Ø SCHED-40 PVC SEWER/
WASTE SOIL PIPE
INVERT LEVEL = - 380 MM FROM PARKING LEVEL
50 MM. Ø PVC GREY WATER PIPE TAPPED TO MAIN WASTE/SOIL PIPE (1.5% SLOPE) UNDER RC SLAB
CO
0' - 11"
285
20 MM.Ø PVC CONDENSATE DRAIN PIPE TAPPED TO PVC GREY WATER PIPE AT BELOW GRADE
1
M−02
MECHANICAL ELEVATIONS
1 : 50
FRONT ELEVATION
TOP OF PARAPET WALL 9775
6759 22' - 2"
100 MM. Ø PVC ROOF VENT CAP
75 MM. Ø FULLBORRE ROOF DRAIN
TOP OF ROOF DECK
7104
75MM. Ø PVC RAIN LEADER FROM ROOF DECK BEHIND MASONRY WALL, PROVIDE DRYWALL CLADDING - SEE DETAIL
ACCU W/ 100 MM. HT. CONCRETE PLINTH
BLOCKWALL RAILING HT.
EXTRACTOR FAN GRILLE W/ PVC VENT PIPE INSIDE CEILING
20 MM.Ø PVC CONDENSATE DRAIN EMBEDDED IN WALL RECOMMENDED CEILING LEVEL
AC CLG#02 OUTLINE
669
100 MM. Ø PVC VENT THRU ROOF PIPE
2671
8' - 9"
21' - 8"
9' - 0"
2743
3
M-03M-01
6603
FIRST FLOOR LEVEL
3865
EXTRACTOR FAN GRILLE W/
PVC VENT PIPE INSIDE CEILING
75MM. Ø PVC RAIN KLEADER/ DOWNAPOUT
SCHEDULE 40
9' - 5"
2867
20MM.Ø PVC CONDENSATE DRAINS DISCHARGED TO UTILITY SINK DRAIN AT LAUNDRY ROOM
Ground Floor Level
Parking Level
326
150 26
75MMØ PVC DWV PIPE TO SERVICE BOX DRAINS AT REAR OF PROPERTY
71
20 MM.Ø CONDENSATE DRAINS FROM
AC CLG#02 TAPPED TO WASH BASIN DRAIN IN MASTER'S BATH
2286
7' - 6"
3239
10' - 8"
785
RECOMMENDED CEIL;ING LEVEL
AC CLG# 01 OUTLINE
672
100MM. Ø PVC WASTE STACK/ RISER PIPE-
SCHEDULE 40 (BEHIND CHB WALL) - PROVIDE DRYWALL CLADDING
2411
7' - 11"
3539
11' - 7"
ACCU #01 OUTDOOR UNIT
100 MM.Ø SCHED-40 PVC WASTE/SOIL PIPE = SLOPE 1.25%
CO
50 MM. Ø SCHED-40 PVC LOOP VENT
176
100MM.Ø PVC WASTE /SOIL PIPE FROM POWDER ROOM & LAUNDRY
IL OF 100 MM. Ø SEWER /WASTE SOIL PIPE = - 176MM FROM PARKING LEVEL
REAR ELEVATION
100 0' - 4"
100 MM.Ø S-40 PVC WASTE STACK/ VTR
50 MM.Ø PVC LOOP VENT
103 99
0' - 4"0' - 4"
150 MM. THK MASONRY WALL
150
0' - 6"
300 1' - 0"
50X50 MM.X 1.20 MM METAL STUDS
75MMØ PVC DOWNSPOUT/
RAIN LEADER W/ PVC STRAPS @
1000 MM.O.C.
12.50 MM. MOISTURE RESISTANT
GYPSUM BOARDS ON
METAL STUDS FRAME
100 MMØ PVC WYE + CO
50X50 MM.X 1.20 MM METAL STUDS
12.50 MM. CEMENT BOARDS ON METAL STUDS FRAME
200
0' - 8"
300 1' - 0"
100 MMØ SCHED 40- PVC WASTE PIPE WYE + CLEANOUT
3
M−02
GB CLADDING DETAILS
1 : 10
2
M−02
CB CLADDING DETAILS
1 : 10
NOTES:
GENERAL:
1.ALL WORKS TO BE CONSTRUCTED BY A
SANITARY CONSTRUCTOR LICENSED BY
THE WATER AND SEWAGE AUTHORITY OF
TRINIDAD & TOBAGO.
2.ALL WORKS SHALL COMPLY WITH: THE
NATIONAL PLUMBING CODE OF TRINIDAD
& TOBAGO.
3.
THE LICENSED SANITARY CONSTRUCTOR SHALL ENSURE THAT WASA'S
REPRESENTATIVE SHALL INSPECT AND APPROVE ALL STAGES OF THE WORKS AND SHALL OBTAIN FINAL APPROVAL.
4.ALL GRAVITY PIPES AND FITTINGS SHALL
MEET THE REQUIREMENTS AND COMPLIANT
WITH ASTM 2665
5.ALL PRESSURE PIPES :AND FITTINGS
SHALL BE PVC SCHEDULE 40.
POTABLE WATER SYSTEM :
1.ALL MATERIALS SHALL CONFORM WITH
THE FOLLOWING BRITISH OR EQUIVALENT
AMERICAN STANDARDS CODES.
(A) BS EN 1452-1: 2000 GENERAL
(B) BS EN 1452-2: 2000 PIPES
(C) BS EN 1452-3: 2000 FITTINGS
2.ALL FIXTURES ARE TO BE PROVIDED
WITH ANGLE GATE VALVES
3.THE OVERFLOW TO ALL WATER CLOSETS
TO BE PIPED TO THE OUTSIDE OF THE
BUILDING.
4.EACH SUPPLY BRANCHES SHALL HAVE AN
ISOLATING GATE VALVES.
5.ALL PIPES ARE TO BE PRESSURE TESTED
AND CAPPED OFF IN SEGMENTS BEFORE
COVER UP AND FINAL COMMISIONING.
DRAIN, WASTE & VENT SYSTEM
ALL PRESSURE PIPES AND FITTINGS
1.
SHALL BE PVC SCHEDULE 40.
2.ALL PIPES UNDER BUILDING OR UNDER
CONCRETE SLAB TO BE SCHEDULE-80
PVC PIPES.
3.GRADES TO PIPE AS FOLLOWS:
(A)100∅ PIPE = 4 : 300
(B)150∅ PIPE = 6 : 300
4.CLEANOUT TO BE PLACED EVERY
1500MM APART.
DRAWING ISSUE:
PROMOTIONAL INFORMATION
RE VISION:
ISSUE: REVISION:
DATE
MM:DD:YY
DRAWING TITLE:
ELEVATIONS- AC & ACCU
DESIGNED DRAWN CHECKED
DATE
SCALE
PROJECT:
APR / RFMaraya LITEDARCH
DBrooks
Issue Date
As indicated
20 No. TOWNHOUSES
DRWG.#
M-02
T.Q. REF.#
EverGreen by Andoma
Lot Nos. 1 & 2a,
Warren Road, Chaguanas.
CLIENT:
APR ASSOCIATES LIMITED
32 AGOSTINI STREET, ST. JOSEPH
APR ASSOCIATES LIMITED E P MANAGERS.
NGINEERS &ROJECT
#32 Agostini Street,
St. Joseph,
Trinidad West Indies. Phone:(868) 663-5171
Fax: (868) 662-1667
203
8"
1050 MM.
3' - 3"
TOP OF ROOF DECK 7104
103 MM. THICK CONCRETE PLINTH FOR AC CONDENSING UNITS
ACCU #03
PROVIDE PVC TRUNK COVER FOR INSULATED REFRIGERANT LINES MOUNTED INSIDE CEILING AND UNDERSIDE OF ROOF DECK CONCRETE SLAB
3239
10' - 8"
SLIDING SASH uPVC WINDOWS W/ GREEN FLOAT GLASS
FIRST FLOOR LEVEL 3865
ISOLATOR SWITCH
POWER SUPPLY TO AIR CONDITIONING UNIT IN PVC CONDUIT PIPE EMBEDDED IN MASONRY WALL
ENTERTAINMENT AREA
250 X 600 MM RC FLOOR BEAM
103
4"
ACU CLG #03
INSULATED REFRIGERANT PIPE LINES
FROM AC CLG UNIT TO OUTDOOR ACCU
CEILING LEVEL
10 MM. GYPSUM CEILING BOARDS
ON METAL FURING @ 400 MM.O.C.
4,500 BTU CEILING TYPE
SPLIT AIR CONDITIONER
20MM.Ø PVC CONDENSATE DRAINS
INSIDE MASONRY WALL- TAPPED /
DRAIN AT NEARBY DOWNSPOUT
2264
7' - 5"
2629
8' - 8"
BEDROOM 03
KITCHEN
FIRST FLOOR & ROOF DECK LEVEL AIRCON DETAILS @ ACCU#03
NOTES:
MAIN VENT PIPE VENT THRU ROOF (V TR)
FIRST FLOOR LEVEL 3865
1% SLOPE FOR WASTE PIPE FROM TOILET
S @ FIRST FLOOR
CO
10 MM. GYPSUM CEILING BOARDS ON METAL FURING @ 400 MM.O.C.
FLOOR TO FLOOR HEIGHT = 11' 2"
AC CLG#01
2743
ACU MOUNTING HEIGHT
20,800 BTU (MIN.) CEILING TYPE
SPLIT AIR CONDITIONER
INSULATED REFRIGERANT PIPE LINES
INSIDE PVC TRUNKING ( SURFACE MOUNTED)
FROM ACCU TO CEILING TYPE ACU
25MM.Ø PVC CONDENSATE DRAINS
INSIDE MASONRY WALL- 100 MM BESIDE
DOOR FRAME- DRAIN AT UTILITY SINK
AT LAUNDRY ROOM
9' - 0"
2300 MM.
7' - 7"
LIVING ROOM
915 MM.
3'-0"
ISOLATOR SWITCH
REINFORCED 150 MM. THICK MASONRY WALL WING
PROVIDE PVC TRUNK CIOVER FOR INSULATED
REFRIGERANT LINES MOUNTED INSIDE CEILING
AND UNDERSIDE OF ROOF DECK CONCRETE SLAB
ACU & ACCU POWER SUPPLY CABLE INSIDE 19MM.Ø PVC CONDUIT PIPE EMBEDDED IN MASONRY WING WALL
100 MM.Ø SCHEDULE 40 POVC WASTE STACK & VENT THRU ROOF (VTR)- (SEE PLUMBING DRAWINGS)
GENERAL:
1.ALL WORKS TO BE CONSTRUCTED BY A
SANITARY CONSTRUCTOR LICENSED BY
THE WATER AND SEWAGE AUTHORITY OF
TRINIDAD & TOBAGO.
2.ALL WORKS SHALL COMPLY WITH: THE
NATIONAL PLUMBING CODE OF TRINIDAD
& TOBAGO.
3.
THE LICENSED SANITARY CONSTRUCTOR SHALL ENSURE THAT WASA'S
REPRESENTATIVE SHALL INSPECT AND APPROVE ALL STAGES OF THE WORKS AND SHALL OBTAIN FINAL APPROVAL.
4.ALL GRAVITY PIPES AND FITTINGS SHALL
MEET THE REQUIREMENTS AND COMPLIANT
WITH ASTM 2665
5.ALL PRESSURE PIPES :AND FITTINGS
SHALL BE PVC SCHEDULE 40.
POTABLE WATER SYSTEM :
1.ALL MATERIALS SHALL CONFORM WITH
THE FOLLOWING BRITISH OR EQUIVALENT
AMERICAN STANDARDS CODES.
(A) BS EN 1452-1: 2000 GENERAL
(B) BS EN 1452-2: 2000 PIPES
(C) BS EN 1452-3: 2000 FITTINGS
2.ALL FIXTURES ARE TO BE PROVIDED
WITH ANGLE GATE VALVES
3.THE OVERFLOW TO ALL WATER CLOSETS
TO BE PIPED TO THE OUTSIDE OF THE
BUILDING.
4.EACH SUPPLY BRANCHES SHALL HAVE AN
ISOLATING GATE VALVES.
5.ALL PIPES ARE TO BE PRESSURE TESTED
AND CAPPED OFF IN SEGMENTS BEFORE
COVER UP AND FINAL COMMISIONING.
DRAIN, WASTE & VENT SYSTEM
ALL PRESSURE PIPES AND FITTINGS
1.
SHALL BE PVC SCHEDULE 40.
2.ALL PIPES UNDER BUILDING OR UNDER
CONCRETE SLAB TO BE SCHEDULE-80
PVC PIPES.
3.GRADES TO PIPE AS FOLLOWS:
(A)100∅ PIPE = 4 : 300
(B)150∅ PIPE = 6 : 300
4.CLEANOUT TO BE PLACED EVERY
1500MM APART.
OUTLINE OF DOOR FRAME
Ground Floor Level- Block
326
ACCU#01
INSULATED REFRIGERANT PIPE LINES
INSIDE PVC TRUNKING ( SURFACE MOUNTESD) FROM ACCU TO CEILING TYPE ACU
103 MM. THICK CONCRETE PLINTH
FOR AC CONDENSING UNITS
100
Parking Level
0' - 4"
GROUND FLOOR
AIRCON DETAILS @ ACCU#01
700
2' - 4"
DRAWING ISSUE:
PROMOTIONAL INFORMATION
RE VISION:
ISSUE: REVISION:
DATE
MM:DD:YY
DRAWING TITLE:
AIRCON DETAILS
DESIGNED DRAWN CHECKED
DATE
SCALE
PROJECT:
APR / RFMaraya LITEDARCH
DBrooks
Issue Date
1 : 20
20 No. TOWNHOUSES
DRWG.#
M-03
T.Q. REF.#
EverGreen by Andoma
Lot Nos. 1 & 2a,
Warren Road, Chaguanas.
CLIENT:
APR ASSOCIATES LIMITED
32 AGOSTINI STREET, ST. JOSEPH
APR ASSOCIATES LIMITED E P MANAGERS.
NGINEERS &ROJECT
#32 Agostini Street,
St. Joseph,
Trinidad West Indies. Phone:(868) 663-5171
Fax: (868) 662-1667